FT6(FZW3A)-12 Outdoor

FT6-12 can be used in outdoor three-phase AC power system of rated voltage 10 (12) kV and rated frequency 50HZ for opening and closing load current, non-load line and non-load transformer.

Features :

  • Vertical rotating structure is used for this kind of product, which can avoid the risk of closing automatically.
  • Vacuum arc-extinguished compartment is equipped in the fully sealed enclosure that operated by high-speed mechanism, and will be not influenced by the outside operation and environment. It can do arc extinguish safety and reliably.
  • The safety of operation is improved by the connection of vacuum arc-chute and isolating control with no possibility of mis-operation. It has obvious fracture that meets the requirements of disconnecting protection. 
  • The material of the exposed components is made of stainless steel, and has long life service. 
  • The characteristics of the switchgear are neat structure, small volume, less weight and simple, reliable mechanism. It can be operated by two methods: manual operation or dual-purpose operation that is manual or electric. It can be used in the automation of network or the operation of sectional device.

The weight of load switchgear: manual or electric operation <=65kg, manual operation<=55kg.

Technical Parameter

No

Item

Unit

Parameter

1

Rated voltage

KV

12

2

Rated frequency

Hz

50

3

Rated current

A

630

4

Rated active load breaking current

A

630

5

Rated closed loop breaking current

A

630

6

5% rated active load breaking current

A

31.5

7

Rated charging breaking current of cable

A

10

8

Rated breaking current of no-load transformer

A

Non-load current of 6000kVA transformer

9

Rated short-time withstand current

KA/s

16/4

10

Rated breaking current of the condenser

A

400

11

Rated peak withstand current

KA

40

12

Rated short-circuit making current

KA

40

13

Rated 1min power frequency withstand voltage (r.m.s) phase to earth, phase-to-phase, vacuum fracture/isolated fracture

KV

42/48

14

Lightning impulse withstand voltage (crest) phase to earth, phase-to-phase, vacuum fracture/isolated fracture

KV

75/85

15

1min wet, withstand voltage earth to earth, phase to phase, isolating point

KV

30/34

16

1min power frequency withstand voltage for isolating point of arc-extinguished compartment

KV

20

17

Mechanical Endurance

Times

2000


Please indicate while ordering:

  • a. The type, name and quantity;
  • b. The installation position, top bar or several meters below the top bar and diameter of bar;
  • c. Operative methods: manual operation or dual-purpose operation that is manual or electric;
  • d. Please keep contact with us , if you have special order.