YBW-24 preinstalled type transformer substation. This series of pre-installed type transformer substation is a high voltage switch equipment, power distribution transformer, the low voltage power distribution equipment according to user requirements, according to a line scheme by the factory, the outdoor type prefabricated forming complete set of equipment.
High voltage switch equipment can choose: ABB, SIEMENS, F&G SF6 of ring net switch cabinets or ISARC and FN type load switch cabinet, can be a terminal or ring network power supply unit; Transformer can choose SC9 type dry type transformer or S9 oil-immersed transformer. Low voltage power distribution equipment imported or domestic famous quality low pressure switch, circuit breakers, ac contactor, each independent units installed perfect control, protection, charged display and stood with lighting system. The cabinet can be installed temperature, humidity automatic control device and forced ventilation system.
This series of pre-installed substation suitable for 7.2 ~ 40.5 kV power supply and the ring network terminal power supply system of city, high buildings, residential area, mines, the subway, dock, hotels, malls, parks, station, school, hospital, oil field, airports, ports and temporary power supply facilities, such as wind power system of power grid connection, road lighting power supply, etc.
Features:
- Outdoor design, long service life.
- Compact design, practical high efficiency.
- Every board and into the VSD deux qualify to dust and moisture into the room.
- The door cover, and side plate with insulating layer, have adiabatic effect.
- Assembly type structure, it is convenient to replace each individual unit.
- Can effectively prevent condensation.
- The shell is made of recyclable materials, accord with environmental protection requirement.
- Use of many design, and harmonious environment.
- main technical parameters
Sequence number |
Project Name |
unit |
Electrical parameters |
|||
High pressure unit |
Rated frequency |
Hz |
50 |
|||
Rated voltage |
kV |
7.2 |
12 |
40.5 |
||
Her mistress rated current line |
A |
630 1250 1600 |
||||
Rated short-term resistance current/time |
kA/s |
20/4 25/3 31.5/4 |
||||
Rated current peak tolerance |
kA |
50 63 80 |
||||
1 min industrial frequency tolerance voltage (of/fracture)) |
kV |
32/36 |
42/48 |
95/115 |
||
Lightning shock resistance voltage (of/fracture) |
kV |
60/70 |
75/85 |
185/215 |
||
Rated short circuit current breaking |
kA |
20 25 31.5 |
||||
Grounding the short circuit current/time tolerance |
kA/s |
20/2 20/4 |
||||
The loop current rated short circuit close |
kA |
50 63 80 |
||||
Rated active load current breaking |
A |
630 |
||||
Rated closed loop current breaking |
A |
630 |
||||
Rated charging cable breaking current |
A |
10 |
||||
Breaking the rated no-load transformer capacity |
kVA |
1250 |
||||
Transfer current rated |
A |
1700 |
||||
Mechanical life |
次 |
3000 |
5000 |
10000 |
||
Low pressure unit |
Rated frequency |
Hz |
50 |
|||
Rated voltage |
kV |
0.4/0.23 |
||||
Insulation rated voltage |
V |
690 |
||||
Rated current of main loop |
A |
100~3200 |
||||
Rated current short-term tolerance |
kA/s |
30/1 50/1 100/1 |
||||
Rated current peak tolerance |
kA |
63 105 176 |
||||
5 s industrial frequency voltage tolerance |
kV |
2.5 |
||||
Lightning shock resistance voltage (of/fracture)) |
kV |
June 8 |
||||
Transformer unit |
type |
|
oil-immersed |
dry |
||
Rated frequency |
Hz |
50 |
||||
Rated voltage |
kV |
12(7.2)/0.4(0.23) |
||||
Rated capacity |
kVA |
30~1600 |
||||
1 min industrial frequency voltage tolerance |
kV |
35(25) |
28(20) |
|||
Lightning shock resistance voltage |
kV |
75(60) |
||||
Impedance voltage |
% |
4 6 |
||||
Points meet range |
|
±x2.5% ±x5% |
||||
Connection group |
|
Y,yn0 D,yn11 |
||||
cabinet |
High and low voltage protection class room |
|
IP33D |
|||
Transformer protection class room |
|
IP23D |
||||
Come to the level (oil-immersed/dry) |
dB |
≤50/55 |
||||
The secondary circuit voltage level |
kV |
1.5/2 |
||||