YBW-24 Substation

YBW-24 preinstalled type transformer substation. This series of pre-installed type transformer substation is a high voltage switch equipment, power distribution transformer, the low voltage power distribution equipment according to user requirements, according to a line scheme by the factory, the outdoor type prefabricated forming complete set of equipment.

High voltage switch equipment can choose: ABB, SIEMENS, F&G SF6 of ring net switch cabinets or ISARC and FN type load switch cabinet, can be a terminal or ring network power supply unit; Transformer can choose SC9 type dry type transformer or S9 oil-immersed transformer. Low voltage power distribution equipment imported or domestic famous quality low pressure switch, circuit breakers, ac contactor, each independent units installed perfect control, protection, charged display and stood with lighting system. The cabinet can be installed temperature, humidity automatic control device and forced ventilation system.

This series of pre-installed substation suitable for 7.2 ~ 40.5 kV power supply and the ring network terminal power supply system of city, high buildings, residential area, mines, the subway, dock, hotels, malls, parks, station, school, hospital, oil field, airports, ports and temporary power supply facilities, such as wind power system of power grid connection, road lighting power supply, etc.

Features:

  1. Outdoor design, long service life.
  2. Compact design, practical high efficiency.
  3. Every board and into the VSD deux qualify to dust and moisture into the room.
  4. The door cover, and side plate with insulating layer, have adiabatic effect.
  5. Assembly type structure, it is convenient to replace each individual unit.
  6. Can effectively prevent condensation.
  7. The shell is made of recyclable materials, accord with environmental protection requirement.
  8. Use of many design, and harmonious environment.
  9. main technical parameters

Sequence number

Project Name

unit

Electrical parameters

High pressure unit

Rated frequency

Hz

50

Rated voltage

kV

7.2

12

40.5

Her mistress rated current line

A

630 1250 1600

Rated short-term resistance current/time

kA/s

20/4 25/3 31.5/4

Rated current peak tolerance

kA

50 63 80

1 min industrial frequency tolerance voltage (of/fracture))

kV

32/36

42/48

95/115

Lightning shock resistance voltage (of/fracture)

kV

60/70

75/85

185/215

Rated short circuit current breaking

kA

20 25 31.5

Grounding the short circuit current/time tolerance

kA/s

20/2 20/4

The loop current rated short circuit close

kA

50 63 80

Rated active load current breaking

A

630

Rated closed loop current breaking

A

630

Rated charging cable breaking current

A

10

Breaking the rated no-load transformer capacity

kVA

1250

Transfer current rated

A

1700

Mechanical life

3000

5000

10000

Low pressure unit

Rated frequency

Hz

50

Rated voltage

kV

0.4/0.23

Insulation rated voltage

V

690

Rated current of main loop

A

100~3200

Rated current short-term tolerance

kA/s

30/1 50/1 100/1

Rated current peak tolerance

kA

63 105 176

5 s industrial frequency voltage tolerance

kV

2.5

Lightning shock resistance voltage (of/fracture))

kV

June 8

Transformer unit

type

 

oil-immersed

dry

Rated frequency

Hz

50

Rated voltage

kV

12(7.2)/0.4(0.23)

Rated capacity

kVA

30~1600

1 min industrial frequency voltage tolerance

kV

35(25)

28(20)

Lightning shock resistance voltage

kV

75(60)

Impedance voltage

%

4 6

Points meet range

 

±x2.5% ±x5%

Connection group

 

Y,yn0 D,yn11

cabinet

High and low voltage protection class room

 

IP33D

Transformer protection class room

 

IP23D

Come to the level (oil-immersed/dry)

dB

≤50/55

The secondary circuit voltage level

kV

1.5/2