Mobile menu

JCZR-12 Vacuum Contactor 3p

JCZR-12 series indoor withdrawable AC Vacuum Contactor 3 polesis suitable for the AC electric system, of which the frequency is 50~60 Hz, rated working voltage of 12 kV (or 7.2 kV), for direct or remote on-off control of the main circuits.

This series of vacuum contactors can be mounted in the switchgear to form F-C circuit, matched with integrate protection device. It is used for making and breaking the load of AC H.V. motors, transformers, and capacitors in the power-plants, industrial and mining establishments. It also has functions of over-load protection and short-circuit protection. This combined appliance can be used in tri-phase power system of AC 50Hz.

INDOOR H.V. VACUUM CONTACTOR-FUSE COMBINED APPLIANCE

WORKING CONDITIONS

1) Ambient temperature: Maximum ambient air temperature not exceeds +40℃; averaged air temperature within 24 hours not exceeds +35℃; minimum ambient temperature to be not lower than -15℃.

2) Altitude above sea level: altitude above sea level of the installation place not exceeds 1,000 m.

3) Relative humidity: relative humidity of the atmospheric air not exceeds 50% when the ambient air temperature is +40℃; higher relative humidity is allowed when the air temperature is lower, daily averaged relative humidity not exceeds 95%; maximum monthly averaged relative humidity is 90% when the averaged air temperature is +20℃in most humid months. Having taken into account the condensation dew on the surface of the product due to the temperature variation.

4) Working conditions: the places where are without the invasion of rain or snow, without open fire and explosive danger, without chemical corrosions and strong vibration.

WORKING PRINCIPLES

  • In the contactor-fuse combined appliance, fuse is upper and contactor is lower, both are installed on the trolley.
  • Fuse is installed at the power-supply side of contactor.
  • Fuse striker operating will drive the contactor electric open, and the closing circuit be cut off.
  • The trolley in-and-out adopts lead-screw feeding mechanism, which can realize closing-door operation.
  • Interlocking function is complete, and the design is reasonable.

You can asking Data Sheet List before order by e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it.  or This email address is being protected from spambots. You need JavaScript enabled to view it.